|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[A]
Compressor will not start, no humming

|
1
|
Line
Disconnect switch open
|
Close to
start.
|
|
2
|
Fuse Removed
or Blown
|
Replace fuse.
|
|
3
|
Overload
Protector Tripped
|
Refer to
electrical section.
|
|
4
|
Defective
Wiring
|
Repair or
replace.
|
|
5
|
Control stock
in open position
|
Repair or
replace.
|
|
6
|
Control off
due to cold location
|
Relocate
control.
|
|
7
|
Control
defective
|
Repair or
replace.
|
|
8
|
Wiring
improper or loose
|
Check wiring
against diagram
|
|
9
|
No power to
unit
|
Check main
circuit breaker.
|
|
10
|
Overload
protector incorrect or defective
|
Replace with
correct one.
|
|
11
|
Compressor
motor or mechanism defective
|
Repair or
replace.
|
|
12
|
Defective
Thermostat, Contactor, Transformer or Control relay.
|
Replace
component.
|
|
13
|
Insufficient
line voltage
|
Determine
cause and correct.
|
|
14
|
Thermostat
setting to high
|
Lower
thermostat setting below room temperature.
|
|
15
|
High Pressure
switch tripped
|
See problem
"Excessive head pressure.
|
|
16
|
Low pressure
switch tripped
|
Check for
leaks, repair and recharge.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[B]
Compressor will not start, hums but cycles on overload
protector

|
1
|
Improperly
wired
|
Check wiring
against wiring diagram.
|
|
2
|
Low voltage
to unit.
|
Call trained
electrician or power company.
|
|
3
|
Start
capacitor defective.
|
Determine
reason and replace.
|
|
4
|
Relay
contacts not closing.
|
Determine
reason and replace.
|
|
5
|
Compressor
motor has a winding open or shorted.
|
Replace
compressor.
|
|
6
|
High head
pressure.
|
Replace
filter, clean coil, remove excessive refrigerant.
|
|
7
|
Internal
mechanical trouble in compressor, low oil charge.
|
Correct or
replace.
|
|
8
|
Compressor
grounded
|
Determine
reason and correct.
|
|
9
|
Overload
protector incorrect or defective
|
Replace
overload.
|
|
10
|
Compressor
motor requires start assist.
|
Try start
assist.
|
|
11
|
System
not equalized |
Wait
5mins before restart. |
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[C]
Compressor starts but does not switch off of starting
windings

|
1
|
Improperly
wired
|
Check wiring
against wiring diagram.
|
|
2
|
Low voltage
on unit
|
Determine
reason and correct.
|
|
3
|
Relay failing
to open
|
Determine
reason and correct.
|
|
4
|
Run capacitor
defective
|
Replace
|
|
5
|
Start
capacitor weak
|
Replace
|
|
6
|
High head
pressure
|
Refer to (Q)
|
|
7
|
Compressor
motor has a winding open or shorted.
|
Replace
compressor.
|
| 8 |
Internal
mechanical trouble in compressor. |
Replace
compressor. |
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[D]
Compressor starts and runs but cycles on overload protector

|
1
|
Additional
current passing through overload protector.
|
Check
diagrams for items added to wrong side of protector.
|
|
2
|
Low voltage
to unit (or unbalance if three phase).
|
Determine
reason and correct.
|
|
3
|
Overload
protector defective.
|
Replace after
checking current.
|
|
4
|
Run capacitor
defective.
|
Determine
reason and correct.
|
|
5
|
High head
pressure.
|
Check
ventilation for restrictions in refrigeration system.
|
|
6
|
Compressor
gas hot- return gas hot.
|
Check for
leaks, add refrigerant if necessary.
|
|
7
|
Compressor
motor has a winding shorted or partially grounded.
|
Replace
compressor.
|
|
8
|
Bearings or
pistons tight, low oil charge.
|
Correct or
replace.
|
|
9
|
Air or non
condensable gases in system
|
Reclaim gas,
evacuate and charge to nameplate.
|
|
10
|
Capillary
tube or strainer restricted.
|
Repair and
replace capillary and strainer.
|
|
11
|
Refrigerant
overcharge
|
Recharge to
nameplate.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[E]
Unit runs fine but short cycles

|
1
|
Overload
protector
|
Refer to (D).
|
|
2
|
Thermostat.
|
Differential
set to close (widen).
|
|
3
|
High pressure
cutout due to:
|
|
|
(a) High head
pressure.
|
Refer to (Q).
|
|
(b)
Insufficient air or water supply.
|
Check air or
water supply.
|
|
(c)
Undercharge of refrigerant.
|
Fix leak, add
refrigerant.
|
|
(d) Air in
system.
|
Purge.
|
|
(e) Internal
mechanical trouble in compressor.
|
Replace
compressor.
|
|
4
|
Low pressure
cutout due to:
|
|
|
(a) liquid
line solenoid leaking.
|
Replace.
|
|
(b)
Compressor discharge valves leaking.
|
Replace.
|
|
(c)
Undercharge of refrigerant.
|
Fix leak, add
refrigerant.
|
|
(d)
Restriction in expansion valve.
|
Replace.
|
|
(e) Expansion
valve leaking.
|
Replace.
|
|
5
|
Low voltage.
|
Check voltage
at main panel.
|
|
6
|
Capacitor
incorrect or defective.
|
Replace with
correct mfd.
|
|
7
|
System not
equalized.
|
Wait 5mins
before restart.
|
|
8
|
Improper
louver setting.
|
Deflect
louver away from intake.
|
|
9
|
Fan motor to
slow.
|
Replace with
rated rpm and hp.
|
|
10
|
Unit over
sized for application.
|
Resize
according to load and size of room.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[F]
Compressor tries to start when thermostat closes but cuts
out on overload, after several attempts finally starts

|
1
|
Low voltage
|
Determine
reason and correct.
|
|
2
|
Thermostat
differential to close
|
Increase
differential.
|
|
3
|
Thermostat
bulb not tight contact with evaporator.
|
Tighten
contact.
|
|
4
|
Defective
relay (contacts pitted)
|
Replace.
|
|
5
|
Starting
capacitor defective or incorrect.
|
Replace.
|
|
6
|
Slight
restriction in capillary tube strainer or drier.
|
Replace item.
|
|
7
|
Air or non-condensables
in system.
|
Purge if
minor or replace contaminated refrigerant with new charge.
Use high vacuum to process complete system.
|
|
8
|
Compressor
motor requires start assist.
|
Try hard
start kit.
|
|
9
|
System not
equalized.
|
Wait 5mins
before restart.
|
|
10
|
Discharge
line restricted.
|
Clear
discharge line.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[G]
Compressor starts but immediately cuts out on overload
|
1
|
Starting
relay contacts welded together.
|
Replace.
|
|
2
|
Starting
capacitor defective.
|
Replace.
|
|
3
|
Low voltage.
|
Determine
reason and correct.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[H]
Unit operates long or continuously

|
1
|
Shortage of
refrigerant.
|
Repair leak
add refrigerant.
|
|
2
|
Control
contacts stuck or frozen closed.
|
Clear
contacts or replace control.
|
|
3
|
Refrigerated
or air-conditioned space has excessive load or poor
insulation.
|
Determine
fault and correct.
|
|
4
|
System
inadequate to handle load.
|
Replace with
larger system.
|
|
5
|
Evaporator
iced or dirty
|
Defrost and
clean.
|
|
6
|
Restriction
in refrigeration system.
|
Determine
fault and correct.
|
|
7
|
Dirty or
restricted condenser.
|
Clean.
|
|
8
|
Filter dirty.
|
Clean or
replace.
|
|
9
|
Unit location
to warm.
|
Check
ventilation, relocate unit if necessary.
|
|
10
|
Air or
non-condensable gases in system.
|
Refer to F7
|
|
11
|
Expansion
valve plugged or defective
|
Clean or
replace.
|
|
12
|
Fixture doors
left open to long.
|
Caution owner
or user.
|
|
13
|
Insufficient,
defective or waterlogged insulation.
|
Determine
fault and correct.
|
|
14
|
Compressor
inefficient.
|
Replace
compressor.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[I]
Start capacitor open, shorted or blown

|
1
|
Relay
contacts not opening properly.
|
Replace.
|
|
2
|
Prolong
operation in start cycle due to:
|
|
|
(a) Low
voltage to unit.
|
Determine
reason and correct.
|
|
(b) Improper
relay.
|
Replace.
|
|
(c) Starting
load too high.
|
Correct by
using pump down arrangement if necessary.
|
|
3
|
Excessive
short cycling.
|
Refer to E
1,2,3 and 4.
|
|
4
|
Improper
capacitor.
|
Replace.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[J]
Run capacitor open, shorted or blown

|
1
|
Relay
contacts not opening properly
|
Replace.
|
|
2
|
Prolong
operation on start cycle due to:
|
|
|
(a) Low
voltage to unit.
|
Determine
reason and correct.
|
|
(b) Improper
relay.
|
Replace.
|
|
(c) Starting
load to high.
|
Correct by
using pump-down arrangement if necessary.
|
|
3
|
Excessive
short cycling
|
Refer to E
1,2,3 and 4
|
|
4
|
Improper
capacitor
|
Replace.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[K]
Start relay defective or burnt out

|
1
|
Line voltage
too high or to low.
|
Determine
reason and correct.
|
|
2
|
Incorrect
relay.
|
Determine
correct type and replace.
|
|
3
|
Incorrect
mounting angle.
|
Remount relay
in correct position.
|
|
4
|
Excessive
short cycling
|
Refer to E
1,2,3 and 4
|
|
5
|
Relay being
influence by loose vibrating mount.
|
Remount and
tighten.
|
|
6
|
Incorrect run
capacitor.
|
Replace
capacitor.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[L]
Refrigerated space temperature too high

|
1
|
Shortage of
refrigerant.
|
Locate leak
add refrigerant.
|
|
2
|
Restricted
capillary tube strainer or drier.
|
Use capillary
tube cleaner or replace item.
|
|
3
|
Control
setting to high.
|
Reset
control.
|
|
4
|
Expansion
valve or cooling coil too small.
|
Replace or
add surface to coil.
|
|
5
|
Expansion
valve restricted or defective.
|
Replace or
repair.
|
|
6
|
Refrigerant
lines too small.
|
Determine
correct size and replace.
|
|
7
|
Unit too
small for application.
|
Determine
correct size and replace.
|
|
8
|
Inadequate
air circulation.
|
Improve air
movement.
|
|
9
|
Evaporator
coil plugged with ice or dirty.
|
Defrost and
clean.
|
|
10
|
Evaporator
oil logged.
|
Apply mild
heat to evaporator and pump down if necessary.
|
|
11
|
Inefficient
compressor.
|
Replace.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[M]
Suction line frosted or sweating

|
1
|
Expansion
valve passing excessive or is over sized.
|
Readjust
valve or replace with smaller valve.
|
|
2
|
Expansion
valve stuck open.
|
Clean valve
or replace.
|
|
3
|
Evaporator
fan not running.
|
Determine
reason and correct.
|
|
4
|
Overcharge of
refrigerant.
|
Reduce to
correct charge.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[N]
Liquid line frosted or sweating

|
1
|
Restriction
in dehydrator or strainer.
|
Replace part.
|
|
2
|
Shutoff valve
on receiver either partially closed or restricted.
|
Open valve
fully.
|
|
3
|
Solenoid
valve leaking.
|
Replace part.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[O]
Unit noisy

|
1
|
Loose or
mounting.
|
Locate and
tighten.
|
|
2
|
Tubing
rattle.
|
Reform to
clear.
|
|
3
|
Bent fan
blade causing vibration.
|
Replace
blade.
|
|
4
|
Fan motor
bearings worn.
|
Replace
motor.
|
|
5
|
Compressor
oil charge low.
|
Add oil.
|
|
6
|
Refrigerant
overcharge.
|
Reduce
refrigerant.
|
|
7
|
Improper unit
installation.
|
Install
properly.
|
|
8
|
Dirty air
filter.
|
Clean.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[P]
Evaporator freezes but defrosts while unit is running

|
1
|
Moisture
|
Release
contaminated refrigerant. Use triple sweep with high vacuum
pump for dehydration.
|
|
2
|
Sticking or
corroded valve.
|
Replace.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[Q]
Head pressure to high

|
1
|
Unit
overcharge
|
Reduce
refrigerant charge.
|
|
2
|
Air or
non-condensable in system.
|
Refer to F7
|
|
3
|
Defective
condenser fan motor.
|
Replace
motor.
|
|
4
|
Unit location
too hot.
|
Check
ventilation, relocate unit if necessary.
|
|
5
|
Restriction
in water cooled condenser.
|
Locate and
correct, replace if necessary.
|
|
6
|
Water supply
shut off.
|
Determine
reason and correct.
|
|
7
|
Restriction
in capillary tube, strainer or drier.
|
Replace part.
|
|
8
|
Discharge
valve partially closed.
|
Open valve
fully.
|
|
9
|
Restriction
in discharge line.
|
Locate and
correct.
|
|
10
|
High ambient
temperature
|
Make sure
area is properly ventilated or relocate unit.
|
|
11
|
Indoor sensor
faulty
|
Replace.
|
|
Problem
|
No.
|
Possible
Cause
|
Possible
solution
|
|
[R]
Head pressure to low

|
1
|
Insufficient
refrigerant charge.
|
Find leak add
refrigerant.
|
|
2
|
Leak in
system.
|
Locate,
repair and add refrigerant.
|
|
3
|
Unit in cold
location.
|
Check
ventilation, relocate unit if necessary.
|
|
4
|
Cooling water
to cold.
|
Determine
reason and correct with new connection if necessary.
|
|
|